Authors:
I Wayan Jondra
;
I Sunaya
and
I Wiryawan
Affiliation:
Electrical Departmen, Politeknik Negeri Bali, Bukit Jimbaran, Badung, Indonesia
Keyword(s):
Electrical, Grounding Tool, Work Safety.
Abstract:
In this globalization Electrical energy has become like a primary need. Electrical energy consumption growth has coherency with economic growth. The electricity supply system is designed to improve the reliability without blackout. Reliability improvement can be done by construction, maintenance, repair and improvement of the system. Construction, maintenance, repair and improvement of the distribution system must be guaranteed work safety and health. In Australia, electrical safety and health are very tightly regulated, because it very dangerous if the equipment is not grounded properly. The preparation of electrical safety grounding for medium voltage distribution with A3CS cables is very important, because now only available for A3C cables. This research is quantitative research through statistical and mathematical data processing. This study examines the feasibility of electrical ground safety assembled for medium voltage distribution with A3CS cables. The results found that elec
trical safety grounding tools is feasible to use in construction, maintenance, repair and improvement of over head medium voltage distribution system with A3CS and A3C cable. This grounding tools has an insulation resistance more than 100 mega ohms, a leakage current smaller than 1 milli amperes, and the distance of workers to the active part is more than 0.9 meters.
(More)