![](bg8.png)
***********LINE FLOW SUMMARY ********
FROM TO
5 p
UR
US #1 EF BUS
R
0.0000
OAD_L1 US #1
.9
R
.0000
OAD_L2 BUS #1
3 0.
UR
0 0.0000
OAD_L3 US #1
V
R
REF BUS BUS #1 852 0.0000
Figure 10: State Estimator Results for 0.5 milliohm Series
LOAD #1 increases to
4.8
est weighted error
always
(pU)
BUS 1 BUS #1 V= 0.98 .u.
MEAS E NORM ERROR
BUS #1 LOAD_L1 P,pu 0.0694 0.0000
BUS #1 LOAD_L1 I,pu 0.0705 0.0000
BUS #1 LOAD_L1 Q,pu 0.0000 0.0000
BUS #1 LOAD_L1 V,pu 0.9851 0.0000
BUS #1 LOAD_L2 P,pu 0.0386 0.0000
BUS #1 LOAD_L2 I,pu 0.0392 0.0000
BUS #1 LOAD_L2 Q,pu 0.0000 0.0000
BUS #1 LOAD_L2 V,pu 0.9851 0.0000
BUS #1 LOAD_L3 P,pu 0.0793 0.0000
BUS #1 LOAD_L3 I,pu 0.0805 0.0000
BUS #1 LOAD_L3 Q,pu 0.0000 0.0000
BUS #1 LOAD_L3 V,pu 0.9851 0.0000
BUS #1 REF BUS P,pu -0.1852 0.0001
BUS #1 REF BUS I,pu -0.1880 0.0001
BUS #1 REF BUS Q,pu -0.0000 0.0000
B R V,pu 0.9851 0.0000
BUS 2 LOAD_L1 V= 0.985 p.u.
MEASU E NORM ERROR
LOAD_L1 BUS #1 P,pu -0.0694 0.0000
LOAD_L1 BUS #1 I,pu -0.0705 0.0000
LOAD_L1 BUS #1 Q,pu -0.0000
L B V,pu 0.9844 0.0004
BUS 3 LOAD_L2 V= 0 85 p.u.
MEASU E NORM ERROR
LOAD_L2 BUS #1 P,pu -0.0386 0.0000
LOAD_L2 BUS #1 I,pu -0.0392 0.0000
LOAD_L2 BUS #1 Q,pu -0.0000 0
L V,pu 0.9848 0.0000
BUS 4 LOAD_L V= 984 p.u.
MEAS E NORM ERROR
LOAD_L3 BUS #1 P,pu -0.0793 0.0000
LOAD_L3 BUS #1 I,pu -0.0805 0.0000
LOAD_L3 BUS #1 Q,pu -0.000
L B V,pu 0.9846 0.0001
BUS 5 REF BUS = 0.985 p.u.
MEASU E NORM ERROR
REF BUS BUS #1 P,pu 0.1852 0.0001
REF BUS BUS #1 I,pu 0.1880 0.0001
REF BUS BUS #1 Q,pu 0.0000 0.0000
V,pu 0.9
Fault in Line #1
The normalized voltage error in transmission #1
at LOAD #1 has a value 4 X 10
-4
so line #1 is
identified as the ‘faulted’ transmission line because
it has a much higher residual than the criterion of 4.1
X10
-5
of normal operation. When the fault
magnitude is increased to 5.0 milliohms, the
normalized voltage error at
X10
-4
, so the detection is relatively insensitive to
the magnitude of the fault.
The line where the fault is located, so long as
normalized error is above the minimum level, or a
threshold set from the base case (no fault condition).
To treat the case of multiple normalized errors above
the minimum level, the errors are weighted and
propagated through the network to find the largest
weighted error. This larg
cor
10
and
3.3 X10
respectively. It is necessary to eliminate
the ‘bad data’ before series fault detection.
ctions. When the normalized
res
t (dc system only) are above the threshold
for bad data, then the line has a shunt fault to
ground.
utual coupling. The added weight for
sin
responds to the faulted line. The line with the
fault is always detected.
This fault example has considered all data in the
‘snapshot’, equation 11, to be valid. ‘Bad data’
errors could originate in electronic equipment
failures in the voltage transducers, current
transducers, A/D converters, data acquisition,
memory, and other sources. For example, the valid
voltage measurement at bus #2 is 265.972. If this
voltage value is changed to 264.972 or 266.972, then
the normalized residual increases to 4.1 X
-3
-3
6 OTHER FAULTS
Bus faults are detected as bad data for zero injection
values at the bus. For example, if all the
transmission line power flows from a bus are
measured the sum is zero, therefore P
i
= 0, Q
i
= 0,
|I
i
|= 0 for the inje
idual of these injections is the largest of residuals,
the bus has faulted.
Transmission line to ground faults are detected
by means of the residuals at the ends of the line. If
the residuals for real power flow (ac or dc systems)
or curren
7 CONCLUDING REMARKS
The dc example is a special case of the 3-phase ac
case where the line flows and the fault is balanced.
To detect a single phase fault on a 3-phase system,
each phase must be instrumented and the State
Estimator algorithm must be extended to single
phase with m
gle phase transducer measurements may be
prohibitive.
State Estimation power flow depends on small
voltage differences, and small phase angle
differences for the ac case, such that differential
voltage measuring methods should be used.
ICINCO 2004 - ROBOTICS AND AUTOMATION
140