time, e. g. three times a day for two hours (in Austria
and Germany). ERCS are also used to manage
high/low tariffs where electricity consumed at night
is less expensive than during the day. This concept is
proved, already implemented and often existing
infrastructure can be used. On the other hand, those
external switching orders could result in a higher
wear of the heat pumps, because ERCS are
mandatory switching orders not considering the heat
pump control and operation strategy. EEBus on the
other hand is a protocol connecting IP-based devices
of utilities and distribution service operators (DSOs)
with the not yet IP-based devices of end customers.
For smart control of end user devices the KNX and
ZigBee standards can be used (Koch S. et al.,
2009b). EEBus offers a framework to flexibly
control end-user devices in a household from
external IP-based systems. Typically the devices are
connected to a Home Energy Management System.
Compared to other communication technologies this
is rather expensive and should already be considered
in the construction phase of new buildings. To
subsequently implement this concept for pooling
concepts is rather inappropriate. In Germany exists a
standard called Smart-Grid-ready (SG-ready) label
supported by the German heat pump association. It
is a label specifically designed for heat pumps and is
already implemented in around 370 heat pump
models of 19 different manufacturers. The SG-ready
label defines the operation of heat pumps according
to four operation modes (Bundesverband
Wärmepumpe e. V., 2013, 2015). Mode 1: The heat
pump is switched off for a maximum of two hours.
This includes the already implemented functionality
of interruptible tariffs via ERCS. Mode 2: Here the
heat pump is operated in energy efficient operation
mode according to the local controller taking into
consideration the maximal switching time of two
hours by guaranteeing a certain level of the thermal
storage system. Mode 3: A switching
recommendation is sent to the heat pump to alter its
electrical consumption pattern by modifying the set-
point of the room and/or thermal storage
temperature. It is not an explicit switching order but
a recommendation. Mode 4: The last operation
mode is defined as a compulsory switching order.
Two different mechanisms can be chosen. Either the
compressor of the heat pump (optionally also an
electric heating back-up device) can be directly
switched on or the set-point temperature can be
modified. The main difference to mode 3 is the fact
that the signal is compulsory. Compulsory signals
must be adhered to (mode 1 and 4) and intervene to
some degree into the local heat pump controller.
Switching recommendations leave the control to the
local heat pump controller and only provide
recommendations to alter the consumption pattern of
the heat pump (mode 2 and 3). Regarding mode 4 it
must be considered that directly controlling the
compressor might result in a higher wear of the heat
pump and its components while the control via
temperature set-points is more favourable from
technical view but leaves the exact operation to the
local controller and therefore provides not full
control of the heat pump consumption
(Bundesverband Wärmepumpe e. V., 2013).Of the
above mentioned control mechanisms the SG-ready
label is assumed to be the most favourable because it
is already implemented in many heat pumps and
provides defined operation strategies enabling the
external control of the single heat pump operation.
Moreover it includes the functionality of ERCS and
is considerably cheaper to implement than the
EEBus. The technical concept must guarantee the
conversion of external switching orders in real-time.
This signal S
aggr
is sent by an aggregator resulting
from the participation on the specific electricity
markets. The aggregated consumption of the pool
P
pool
should match the signal S
aggr
. If S
aggr
< P
pool
devices must be switched off until the signal
matches the consumption of the heat pumps. If S
aggr
> P
pool
additional devices must be switched on. In
this context adequate sequencing algorithms are
necessary respecting the actual operational condition
of the single devices. It is favourable to switch those
devices which will be switched in any case in future
due to their normal operation mode. Alternatively a
defined temperature distance to the upper or lower
temperature limit can be used as a sequencing
criterion (Hao et al., 2015; Khan, S., 2016). A smart
box installed at households receives the schedule
and sends adequate orders to the heat pump
corresponding to the SG-ready operation modes 1-4.
The local controller of the heat pump executes the
schedule if possible and sends a feedback of power
P
el
and temperatures T
r
, T
sh
, T
dhw
to the aggregator.
The smart box is basically a communication device
and the link between heat pump and aggregator. The
smart box can be used to subsequently integrate
other residential devices capable of load shifting.
5 CONCLUSIONS
With the use of load shifts the operational costs of a
heat pumps pool can be reduced. In this context it is
important to consider potential efficiency losses
caused by overheating the thermal system. To