Modelling Renewable Energy Sources for Harmonic Assessments in
DIgSILENT PowerFactory: Comparison of Different Approaches
Zhida Deng
1a
, Grazia Todeschini
1b
, Kah Leong Koo
2c
and Maxwell Mulimakwenda
2d
1
Faculty of Science and Engineering, Swansea University, Swansea, U.K.
2
Power Quality and Modelling Department, National Grid, Warwick, U.K.
Keywords: Harmonics, Power Quality, Power Systems Modelling, Renewable Energy Sources, Total Harmonic
Distortion, Voltage Unbalance.
Abstract: With the increasing number of Renewable Energy Sources connected to the power grid, the impact on system
operation is becoming more evident. To assess this impact, accurate computer models are required for both
the power system and the devices connected to it. Various types of system integration studies need to be
performed in order to study both steady-state and abnormal operation. Among the steady-state analyses, power
quality studies assess the impact of Renewable Energy Sources on parameters such as voltage levels and
harmonic content. Harmonic studies are gaining more attention because of the nature of renewable energy
sources which are mainly connected to the power grid through electronic power converters, thus producing
undesirable harmonics. This paper analyses various settings, solvers and harmonic source models in a
commercial software – DIgSILENT PowerFactory – to ensure accurate calculation and correct interpretation
of harmonic assessment. A simple model comprising seven harmonic devices is used for the analysis of
various case studies. Their results are then compared with the standard IEC model and recommendations are
proposed on how to appropriately model the RESs depending on the specific application considered.
1 INTRODUCTION
Existing power systems were designed decades ago
when fossil fuels (e.g. coal, gas, oil) were exclusively
employed to generate electricity. With growing
population and industrial expansion, has led to
increasing demands on power systems pushing them
closer to their operational limits. Challenges to reduce
greenhouse gases from conventional power stations
to tackle climate change have also raised more serious
concerns on the sustainability of fossil fuel-based
power generation. These concerns have fueled the
development of Renewable Energy Sources (RESs)
to meet future electricity demands and displace
conventional generations. It is expected that RESs
will make up to approximately 63.15% of total
installed generation capacity by 2050 in the UK,
according to the National Grid Future Energy
Scenarios report (National Grid ESO, 2019).
a
https://orcid.org/0000-0002-8448-1934
b
https://orcid.org/0000-0001-9411-0726
c
https://orcid.org/0000-0002-9549-8627
d
https://orcid.org/0000-0001-9433-4607
Since conventional power systems have not been
designed to operate not only with large number of
RES devices but also of increasing capacities, power
quality issues need to be managed to an acceptable
level. Increasing harmonic levels is identified as one
of the main areas of concern in relation to RESs
integration, and needs to be well studied and properly
managed, as reported in (Working Group JWG-
C4/C6.29, 2016). The voltage and current are
sinusoidal waveforms in an ideal Alternating Current
(AC) power system but are distorted by harmonics
that are produced by nonlinear loads and power
electronic-based devices, for example motor drives
and RES inverter (IEEE Power and Energy Society,
2014). These devices produce harmonics at multiple
or sub-multiple integers of fundamental frequency.
Small levels of harmonics are tolerated by equipment
and various standards have been developed for
harmonic control and to manage their connection to
the network (Energy Networks Association, 2020;
130
Deng, Z., Todeschini, G., Koo, K. and Mulimakwenda, M.
Modelling Renewable Energy Sources for Harmonic Assessments in DIgSILENT PowerFactory: Comparison of Different Approaches.
DOI: 10.5220/0010580101300140
In Proceedings of the 11th International Conference on Simulation and Modeling Methodologies, Technologies and Applications (SIMULTECH 2021), pages 130-140
ISBN: 978-989-758-528-9
Copyright
c
2021 by SCITEPRESS Science and Technology Publications, Lda. All rights reserved
IEC TR 61000-3-6, 2008; IEEE Power and Energy
Society, 2014). This is because excessive harmonic
levels may lead to various detrimental effects,
including dielectric failure, overheating of electrical
equipment, and false operation of circuit breakers
(Cherian et al., 2016). Since RESs are mainly based
on the use of power electronics, they inject harmonics
into the network. With rapidly increasing number of
these devices, even if individual units are compliant
with the standards, the combined effect of numerous
RESs installed in close proximity will lead to an
overall increase of harmonic levels in the system
(Koo & Emin, 2016).
Computer simulations are used to assess the
impact of RESs on harmonic levels on the network.
Both time-domain and frequency-domain methods
are used (Medina et al., 2013). Time-domain methods
characterise system behaviour using differential
equations, and individual harmonic components can
be derived via Fourier transformation. Although these
methods provide detailed and accurate models of non-
linear devices and their control algorithms, they do
not allow easy calculation of the system impedances
as well as modelling of the frequency-dependent
parameters (Medina et al., 2013).
Frequency-domain analysis methods, including
frequency scans, harmonic penetration studies and
harmonic load flows, are widely employed in
engineering practices to predict expected harmonic
distortions on the network. By performing frequency-
domain analysis, harmonic current and voltage
distortions on the network as well as resonances are
calculated. This process allows assessing compliance
with the standards and, if required, informs on
requirements for the filter design (Working Group
JWC-C4/B4.38, 2019). A frequency scan consists of
calculation of network impedance at various
frequencies to determine frequency responses of
power system and identify potential resonance
conditions; a harmonic penetration study refers to
nodal analysis for each harmonic order assuming no
interaction between fundamental and harmonic
components; a harmonic load flow uses Newton-
Raphson or Gauss-Seidel based algorithm to solve
unified fundamental and harmonic power flow
equations, as described in (Herraiz et al., 2003;
Medina et al., 2013). It is important to observe that in
practice, the terms ‘harmonic load flow’ and
‘harmonic penetration studies’ are often used
interchangeably, but these approaches may produce
different results. Hence, it is important to understand
the assumptions underlying the software and the
solver under consideration.
Frequency-domain analysis can be carried out for
balanced and unbalanced systems. In practical power
systems, unbalance between phases is small from
asymmetry in transmission systems and the nature of
the loads and generating sources are normally
unbalanced, therefore a balanced frequency-domain
analysis is generally sufficient. However, unbalanced
harmonic analysis provides more accurate results
when studying asymmetrical systems, either in terms
of network configuration (Jensen, 2018), and/or
loads. In power systems where RESs are single-phase
connected, it may be necessary to consider unbalance
harmonic distribution between the phases in order to
carry out a more accurate assessment.
In addition to unbalance, the summation of
harmonics due to different sources and harmonic
source modelling is an important factor that will also
has an impact on the accuracy of the results. For
harmonic summation, two approaches are mainly
used: (1) either the magnitude and phase are
considered for each harmonic component, (2) or the
summation rule described in standard IEC 61000-3-6
(IEC TR 61000-3-6, 2008) is employed. In the latter
case, a summation exponent is considered to take into
account harmonic phase angles at higher harmonic
orders. While IEC summation rule is based on
practical considerations, it may result in inaccurate
assessment of harmonic level at the Point of Common
Coupling (PCC) (Eltouki et al., 2018; Working Group
JWG-C4/C6.29, 2016) i.e. at the point where
multiple loads or sources connect to the system. This
discrepancy may be due to the harmonic components
adding or cancelling to varying degrees due to the
harmonic phase angle differences, where this
phenomenon may not be taken into account
accurately when applying the IEC summation rule.
As in (Ghassemi & Koo, 2010), different modelling
approaches are described to calculate the harmonic
distortion at the PCC for an offshore wind farm, and
the limitations of the IEC summation rule are
highlighted.
With large penetration of power converters, such
as the ones used for RESs, it is more likely that
harmonic phase angles will be randomly varying
within a reasonable range (Bećirović et al., 2018).
Under these conditions, it is more appropriate to carry
out harmonic analysis by varying the harmonic phase
angles to provide a more realistic harmonic
assessment. Although the topic of harmonic
assessment for RESs is not new, not many research
works can be found considering the impact of IEC
summation rule, appropriate use of harmonic models,
and system unbalance conditions at the same time.
Modelling Renewable Energy Sources for Harmonic Assessments in DIgSILENT PowerFactory: Comparison of Different Approaches
131
Figure 1: Single-line diagram of the simulated network.
The commercial software DIgSILENT
PowerFactory (DPF) (DIgSILENT, 2020a) is
widely used to perform power quality assessments
and provides numerous options to carry out harmonic
analysis. These options include: harmonic source
models (named IEC source and Unbalance Phase
Correct source), summation rules and solvers. If these
options are not used appropriately to model the actual
equipment, results may vary significantly, thus
leading to misleading harmonic assessments.
Although the user manual (DIgSILENT, 2020b)
briefly explains the differences between these
options, it is not clear enough to understand their
impact on the harmonic assessment.
This work aims at examining the appropriate use
of different harmonic source models and choice of
harmonic load flow solvers available within DPF to
calculate harmonic levels in distribution and
transmission systems. This paper provides a better
understanding of using different options in DPF and
modelling guidance for unbalanced harmonic current
sources in a way that allows flexibility while at the
same time providing comparable results as the ones
provided by the IEC model. DPF is used here as it is
a widely used software in the power industry and
similar concerns may arise with other software.
A simple 9-bus network with 7 harmonic sources
is considered: the network is symmetrical in nature,
and unbalance is caused by the harmonic sources
only. Future work will address unbalanced networks.
In Section 2, the network and harmonic source
models are described. In Section 3, three test cases
with different number of harmonic sources are set up
for harmonic analysis. The frequency scans and
voltage Total Harmonic Distortions (THDs) obtained
from different solvers and harmonic source models
are compared and discussed. Finally, the possibility
of matching IEC harmonic current source model
using equivalent Unbalanced Phase Correct (UPC)
model is investigated.
2 SIMULATION NETWORK AND
HARMONIC SOURCE
2.1 Network Description
A 50 Hz symmetrical three-phase 9-bus network
including 4 transmission lines, two photovoltaics
(PV) plants, 2 Wind Turbine Generator (WTGs), 3
Loads and 5 two-winding Wye grounded-delta (Yg-
d) connected transformers with 30-degree phase shift
was built in DPF, as shown in Figure 1. To ensure
convergence of the power flow at fundamental
frequency, an external grid element acting as slack
bus was used. Distributed-parameter line model was
adopted to consider the long-line effects (i.e. higher
frequencies increase the electrical distance of the line
(Working Group JWC-C4/B4.38, 2019)) during the
harmonic analysis. The voltage levels are indicated
by different colours, and the system component
specifications and power flow parameters are given in
Table 1.
2.2 Harmonic Source Modelling
In this paper, two constant harmonic current source
models available in DPF – UPC and IEC – were
considered. Harmonic current amplitudes (referred to
the fundamental current) up to the 50
th
harmonic
order found from the literature for loads (Preda et al.,
2012; Robinson, 2003), PV farms (Elkholy, 2019;
Erik & Leigh, 2016; Oliver et al., 2018; Rampinelli et
SIMULTECH 2021 - 11th International Conference on Simulation and Modeling Methodologies, Technologies and Applications
132
Table 1: System component parameters.
L1 L2 L3 P1 P2 W1 W2
𝑆
(
MVA
)
20 30 100 12 21 60 30
𝑃
(MW)
19 28.5 90 8 18 40 20
𝑄
(
Mvar
)
6.25 9.37 43.59 0 0 0 0
T1 – T2 T3 – T5
Voltage 400/132 kV 132/33 kV
𝑆
(MVA)
255 90
Z
16% short-circuit
voltage with 1.8 MW
losses
13% short circuit
voltage with 0.25
MW losses
Line1 Line2 Line3 Line4
𝐿
(km)
15 20 24 31
𝑍
(/km)
positive/negative-sequence R and X: 0.0212
and 0.1162;
zero-sequence R and X: 0.0848 and 0.4650
External Grid
Short-circuit power: 10000 MVA;
short circuit current: 14.43 kA; c-factor: 1.1;
R/X ratio: 0.1, R: 1.75 , X: 17.51
Note that the symbols 𝑆
, 𝑃, 𝑄, 𝑍, 𝑅, 𝑋 and 𝐿 denote rated power,
active power, reactive power, impedance resistance, reactance, and
line length, respectively.
al., 2015) and wind farms (Ambrož et al., 2017;
Energyiforsk, 2018; Mendonça et al., 2012; Preciado
et al., 2015; Rauma, 2012) are given in Table 2. The
harmonic data for WTG at 42-50 orders is reported as
smaller than 0.1 in (Ambrož et al., 2017): without
loss of generality, the value of 0.1 was used in this
paper.
Since the harmonic current injection for the IEC
harmonic model in DPF can only be based on the
rated current, the rated current (𝐼
) was chosen as the
reference current for the UPC model to ensure the
same amount of harmonic current injections as the
IEC model. For modelling the IEC harmonic current
source, the data given in Table 2 were used as
harmonic current injections and the standard IEC or
self-defined summation rule can be selected to take
into account the harmonic phase angles. The standard
IEC summation rule is expressed as (IEC TR 61000-
3-6, 2008):
𝐼
=
𝐼

(1)
𝛼=
1 i
f
<5
1.4 i
f
5≤ℎ≤10
2 i
f
>10
(2)
Table 2: Harmonic current injection data.
Load
𝐼
/𝐼
(%)
PV
𝐼
/𝐼
(%)
WTG
𝐼
/𝐼
(%)
Load
𝐼
/𝐼
(%)
PV
𝐼
/𝐼
(%)
WTG
𝐼
/𝐼
(%)
1 100 100 100 26 - 0.04 0.02
2
- 0.11 0.10
27
- 0.02 0.02
3
0.15 0.15 0.10
28
- 0.08 0.02
4
- 0.10 0.10
29
0.11 0.05 0.03
5
0.37 0.16 0.40
30
- 0.05 0.01
6
- 0.03 0.14
31
- 0.11 0.02
7
0.28 0.18 0.07
32
- 0.05 0.01
8
- 0.04 0.06
33
- 0.02 0.02
9
0.27 0.04 0.05
34
0.09 0.03 0.02
10
- 0.04 0.04
35
0.09 0.03 0.04
11
0.41 0.12 0.06
36
- 0.00 0.04
12
- 0.01 0.03
37
- 0.02 0.04
13
0.12 0.11 0.05
38
- 0.01 0.06
14
- 0.03 0.02
39
- 0.08 0.06
15
- 0.02 0.02
40
- 0.10 0.06
16
- 0.02 0.01
41
- 0.13 0.05
17
0.16 0.06 0.03
42
- 0.02 0.10
18
- 0.04 0.01
43
- 0.08 0.10
19
0.08 0.05 0.03
44
- 0.08 0.10
20
- 0.02 0.01
45
- 0.10 0.10
21
0.08 0.02 0.01
46
- 0.02 0.10
22
- 0.02 0.01
47
- 0.11 0.10
23
0.60 0.07 0.02
48
- 0.10 0.10
24
- 0.01 0.01
49
- 0.13 0.10
25
0.08 0.09 0.02
50
- 0.01 0.10
Notation denotes the harmonic order, 𝐼
and 𝐼
refer to
harmonic current at order and reference current, respectively.
where 𝐼
is the harmonic current at

harmonic
order, 𝑁 is the number devices connected at PCC and
𝛼 is the summation exponents for different harmonic
orders.
For modelling the UPC current harmonic sources,
the harmonic current amplitudes of three phases were
set to be identical to allow comparisons with the IEC
model. The actual three-phase harmonic phase angles
of the UPC model are calculated as 𝜑
=∆𝜑
+
ℎ𝜑
, 𝜑
=∆𝜑
+ℎ𝜑
and 𝜑
=∆𝜑
+ℎ𝜑
(DIgSILENT, 2020b), where is the harmonic order,
and 𝜑
, 𝜑
and 𝜑
are the fundament current angles
of phase A, B and C, respectively. The phase
parameters ∆𝜑
, ∆𝜑
and ∆𝜑
used to specify each
harmonic phase angle were set to 0 for positive (e.g.
4, 7, 10, …) and negative-sequence (e.g. 2, 5, 8, …)
orders. Since the triplen harmonics in IEC source are
considered as positive-sequence, the ∆𝜑
, ∆𝜑
and
∆𝜑
in UPC model were set to 0, -120 and 120,
respectively to enable modelling of zero-sequence
components (i.e. triplen harmonics) to be considered
as positive-sequence as in the IEC model. Therefore,
the UPC harmonic source is effectively modelled as a
balanced harmonic model, similar to the IEC
Modelling Renewable Energy Sources for Harmonic Assessments in DIgSILENT PowerFactory: Comparison of Different Approaches
133
Figure 2: Balanced and unbalanced impedance characteristics at B2 for Case 1, Case 3 and Case 3.
Figure 3: Balanced and unbalanced impedance characteristics at B2 of Case 1.
Figure 4: Balanced and unbalanced impedance characteristics at B2 of Case 1 under ideal system conditions.
harmonic source, so that the results from the two
models can be compared.
3 SIMULATION RESULTS AND
DISCUSSION
This section first presents impedance characteristics
obtained from balanced and unbalanced frequency
sweep analysis when IEC and UPC model are used.
Then, various harmonic load flow calculations are
performed using different solvers, to compare the
voltage THD values and examine the differences
between the IEC and the UPC model. Finally, the
possibility of matching the IEC model using an
equivalent UPC model is studied and discussed.
3.1 Frequency Scan Analysis
The frequency scan analysis can be seen as solving
the network equation 𝑰
=𝒀
𝑽
(Medina et al.,
2013). where 𝑰
, 𝑽
and 𝒀
are current vector,
voltage vector and admittance matrix at harmonic
order , respectively. Injecting one pu current and
calculating the corresponding voltage, the system
admittance is obtained. Under the assumption of
system linearity, the frequency scan analysis always
produces the same impedance characteristics
regardless harmonic injection values, the type of
harmonic source model and the number of harmonic
sources. The approach described above is used by
DPF and other commercial software to calculate the
system impedance. In order to verify this assumption,
the balanced and unbalanced frequency scans were
Impedance Z(Ohm)
Impedance Z(Ohm)
0 5 10 15 20 25 30 35 40 45 50
Harmonic Order
0
200
400
600
800
1000
Balanced, Case 1
Unbalanced, Case 1, Zero Sequence
Unbalanced, Case 1, Positive Sequence
Unbalanced, Case 1, Negative Sequence
SIMULTECH 2021 - 11th International Conference on Simulation and Modeling Methodologies, Technologies and Applications
134
calculating by injecting 10 Hz step size harmonic
current up to 2.5 kHz, under following cases:
Case 1: IEC model adopted for 3 loads, 2 PVs
and 2 WTGs.
Case 2: UPC model adopted for the 3 loads, 2
PVs and 2 WTGs.
Case 3: no harmonic source model is
considered.
The impedance characteristics at the 132 kV
busbar B2 for the different cases are presented in
Figure 2. The frequency response at B2 for the tested
cases was exactly the same no matter the type and
number of harmonic sources, and the selection of
balanced or unbalanced frequency scan. These
findings were also verified to other busbars.
In addition to above tests, the impedance
characteristics between balanced and unbalanced
components are compared, as shown in Figure 3.
Although Figure 3 only shows the frequency
characteristics of Case 1, the same results were found
for Case 2 and 3. It can be seen that the balanced,
unbalanced positive-sequence and negative-sequence
share the same impedance characteristics, and their
resonance frequencies occur at the 4
th
, 13
rd
, 24
th
and
48
th
orders. This is because the balanced frequency
scan in DPF considers the positive-sequence
component only. The resonance frequency of
unbalanced zero-sequence shown additional resonant
frequencies at the 8
th
, 31
st
, 37
th
and 43
rd
orders. These
results are expected the resonances of zero-
sequence are shifted when performing unbalanced
frequency scan, mostly due to the Yg-d connection of
the transformers and the difference between and zero
and positive/negative-sequence impedances of the
network components. Based on these considerations,
balanced and unbalanced frequency scans were
performed under an ideal system conditions, where
Yg-Yg connection was used, and positive/negative
and zero-sequence impedances of the transmission
lines and transformers were set to equal, with results
shown in Figure 4. In this case the resonance
frequencies (i.e. 5
th
, 15
th
, and 28
th
harmonic orders) of
balanced and unbalanced components are identical.
The same behaviour was observed for Case 2 and
Case 3. It is therefore concluded that the network
parameters are the only factors influencing the
frequency scans.
3.2 Harmonic Load Flow Analysis
As reviewed in (Herraiz et al., 2003), different
harmonic load flow techniques may produce distinct
results. Therefore, it is necessary to understand which
technique is applied by each software in order to carry
out a correct assessment. For the specific case of DPF,
review of the manual (DIgSILENT, 2020b) and
discussion with the technical support led to conclude
that
the load flow solution is calculated at
fundamental frequency only, and a harmonic
penetration study is carried out by applying nodal
analysis at various harmonic orders. Although a ‘true’
harmonic load flow could provide more accurate
results by taking into account the voltage-dependent
nature of the system components, it requires
significant computational effort due to the process of
solving a large number of fundamental and harmonic
power flow equations simultaneously (Medina et al.,
2013). This may be the reason why harmonic
penetration is widely used in the great majority of
commercial software (Working Group JWC-
C4/B4.38, 2019).
The following three cases were considered to
compare the results of harmonic load flow analysis
using the IEC and the UPC model, based on the
selection of different harmonic load flow solvers
available in DPF:
Case 4: balanced harmonic load flow,
considering positive- or negative-sequence
equivalent single-phase according to default
settings (positive-sequence impedance for
zero- and positive-sequence harmonic orders,
and negative-sequence impedance for
negative-sequence harmonic orders).
Case 5: balanced harmonic load flow with
positive-sequence only (using positive-
sequence impedance for all harmonic orders).
Case 6: unbalanced harmonic load flow that
considers positive or negative-sequence three-
phase components at the related harmonic
order.
When any IEC harmonic source model exists in the
DPF model, the harmonic currents or voltages are
processed using the selected harmonic summation
rule (i.e. with standard or self-defined summation
exponents).
3.2.1 Single Harmonic Source Test
In this test, the photovoltaic plant (P1) connected to
the 33 kV busbar B7 was the only harmonic
producing device in the network. This is a simple way
to verify the differences between IEC and UPC model
when different solvers are used. In Table 3, the
voltage THD values at different busbars for Case 4, 5
Modelling Renewable Energy Sources for Harmonic Assessments in DIgSILENT PowerFactory: Comparison of Different Approaches
135
Table 3: Comparison of THDs between IEC and UPC
models under different cases (single harmonic source).
Standard IEC
model
UPC model
Bus
Case
4&5
(%)
Case 6
3-Ph
(
%
)
Case
4&5
(%)
Case 6
Ph-A
(%)
Case 6
Ph-B
(%)
Case 6
Ph-C
(%)
B1
0.007 0.007 0.006 0.007 0.007 0.007
B2
0.025 0.025 0.023 0.025 0.025 0.025
B3
0.031 0.031 0.027 0.031 0.031 0.031
B4
0.029 0.029 0.026 0.029 0.029 0.029
B5
0.035 0.035 0.030 0.035 0.035 0.035
B6
0.036 0.036 0.032 0.036 0.036 0.036
B7
0.283 0.301 0.241 0.297 0.307 0.292
B8
0.035 0.037 0.030 0.035 0.038 0.037
B9
0.036 0.036 0.032 0.036 0.036 0.036
Bold values are all the same. ‘Ph-A’, ‘Ph-B’, ‘Ph-C’, and ‘3-Phase’
refer to phase A, phase B and phase C and all three phases,
respectively.
Table 4: THDs for IEC and UPC models at low-voltage
busbars under different cases when using Yg-yg
transformers (single harmonic source).
Standard IEC
model
UPC model
Bus
Case
4&5
(%)
Case 6
3-Ph
(
%
)
Case
4&5
(%)
Case 6
Ph-A
(%)
Case 6
Ph-B
(%)
Case 6
Ph-C
(%)
B7 0.283 0.283 0.241 0.283 0.283 0.283
B8
0.035
0.035 0.030 0.035 0.035 0.035
and 6 are obtained, and the following conclusions can
be carried out:
For the standard IEC model, all results are the
same for Case 4, 5 and 6 (three phases), except the
low-voltage busbar B7 and B8, because the use of
Yg-d connection at the 132/33 kV transformers
results in slightly different solutions of the
fundamental load flow for Case 6. By changing
the 132/33 kV transformers to Wye grounded-
wye grounded (Yg-yg) connection, the THDs at
B7 and B8 are the same (bold values in Table 4).
For the UPC model, the results for Case 4 and
Case 5 are different from the IEC model because
the triplen harmonics are ignored. It was verified
that the results for Case 4 and Case 5 using UPC
model were the same as the IEC model when the
IEC model is not considering triplen harmonics.
For the UPC model, the results for Case 6 (phase
A, B and C) are the same as the IEC model, except
at busbar B7 and B8. This is for a similar reason
as discussed above (i.e. transformer connection
resulting in slightly different fundamental power
flow). Table 4 shows the same results when the
transformer connection is modified.
For all cases, the THD values at the high-voltage
busbars are not affected by the transformer
Table 5: Comparison of THDs between IEC and UPC
models for different cases (three harmonic sources).
Standard IEC
model
UPC model
Bus
Case
4&5
(%)
Case 6
3-Ph
(
%
)
Case
4&5
(%)
Case 6
Ph-A
(%)
Case 6
Ph-B
(%)
Case 6
Ph-C
(%)
B1
0.133 0.133 0.145 0.147 0.147 0.147
B2
0.520 0.520 0.564 0.570 0.570 0.570
B3
0.502 0.502 0.546 0.557 0.557 0.557
B4
0.598 0.598 0.640 0.648 0.648 0.648
B5
0.657 0.657 0.692 0.705 0.705 0.705
B6
0.638 0.638 0.677 0.689 0.689 0.689
B7
3.174 3.178 3.148 3.328 3.339 3.311
B8
0.657 0.658 0.692 0.705 0.706 0.705
B9
0.638 0.638 0.676 0.689 0.689 0.689
Table 6: Comparison of THDs between IEC and UPC
models for different cases (three harmonic sources).
Self-defined
IEC Model
UPC Model assessed by standard
IEC summation rule
Bus
Case
4&5
(%)
Case 6
3-Ph
(
%
)
Case
4&5
(%)
Case 6
Ph-A
(%)
Case 6
Ph-B
(%)
Case 6
Ph-C
(%)
B1
0.160 0.160 0.134 0.136 0.136 0.136
B2
0.620 0.620 0.525 0.530 0.530 0.530
B3
0.611 0.611 0.505 0.515 0.515 0.515
B4
0.698 0.698 0.601 0.608 0.608 0.608
B5
0.753 0.753 0.656 0.669 0.669 0.669
B6
0.745 0.745 0.639 0.650 0.650 0.650
B7
3.437 3.495 3.128 3.273 3.278 3.273
B8
0.753 0.757 0.656 0.668 0.669 0.668
B9
0.745 0.745 0.639 0.650 0.650 0.650
connection, the harmonic load flow solver or the
harmonic source model.
The above findings are also applicable to the cases
when other loads, PVs or WTGs are considered
individually.
3.2.2 Three Harmonic Sources at Same
Busbar
In this test, P1, L3 and W1 connected at the 33 kV
busbar B7 were considered as harmonic producing
devices. This test helps to better understand how
multiple harmonic sources are treated under different
cases and models. Note that Yg-d transformers were
considered in this test. In Table 5, the voltage THD
values of IEC model and UPC model at different
busbars under different cases are compared. The THD
values obtained with the standard IEC model under
different cases share similar features as presented in
the single harmonic source test the results of Case 4
and 5 were the same (the bold values in Table 5),
whereas the THDs of Case 6 at B7 and B8 were
slightly different from other cases. The THDs of
UPC model at most busbars (except for B7 and B8)
under Case 4 and 5 were same as Case 6, when
triplen harmonics were not included in Case 6.
SIMULTECH 2021 - 11th International Conference on Simulation and Modeling Methodologies, Technologies and Applications
136
Figure 5: 5
th
harmonic order current flows obtained by using: the standard IEC model (left), the UPC model (middle), and the
UPC model assessed by standard IEC summation rule (right).
The differences between IEC and UPC model can be
explained by observing the use of summation rule,
that takes the cancellation effect between harmonic
sources into account.
In Table 6, the results obtained by applying IEC
model under different cases using a self-defined
summation exponent (i.e. value 1 was used for all
frequencies) are presented. The use of the self-
defined summation exponent leads to larger THDs
because it assumes that all harmonics are in-phase
(i.e. no cancellation effects), while the standard
coefficient implies cancellation effect with increasing
harmonic orders. On the other hand, in DPF, the UPC
model can also be processed using the IEC
summation rule, as long as one harmonic source is
using IEC model. Table 6 indicates that the THDs of
UPC model assessed by the standard IEC summation
rule (i.e. by setting L3 to use IEC model and other two
devices use UPC model) is close to the THDs
obtained from using the standard IEC model (results
of standard IEC model shown in Table 5). The UPC
model applying the standard IEC summation rule
considers both summation rule and harmonic phase
angles, therefore not matching the results obtained
with the standard IEC model.
To understand the causes of the discrepancies, it
is worthwhile to analyse the harmonic current flows
in detail. It is found that the summation of harmonic
currents produced by various sources at the low-
voltage side leads to different results when different
summation rules and harmonic source models are
applied. This is illustrated for the 5
th
harmonic current
as shown in Figure 5, where sources P1, L3 and W1
are considered. The total harmonic current magnitude
obtained for the standard IEC model is 8.901 A (i.e.
0.336
.
+ 6.501
.
+ 4.167
.
.
); for the UPC
model it is 9.978 A, obtained as |0.336 ∠36.325° −
6.501∠ − 92.885°+4.167∠36.325°|. Note that the
harmonic current injection of the load element of
UPC source model is considered in an opposite
direction of the IEC source model in DPF. The last
case in Figure 5 shows the UPC model assessed by
the standard IEC rule, considering both the standard
IEC summation exponent and the UPC angles, thus
leading to a total harmonic current of 9.087 A (i.e.
|0.336
36.325
°
+4.167
36.325
°
|
.
+6.501
.
.
).
When the self-defined summation exponent was used,
the above current flow equations were changed
accordingly.
Given the above results, the UPC model
considering harmonic phase angles may be preferable
under some circumstances, because it allows
modelling the harmonic phase angles in a flexible
way. On the contrary, the IEC model using the
standard summation exponent may put emphasis on
harmonic cancellation, while the phase angles are
fixed. Therefore, the UPC model will generally not
match exactly the standard IEC model, even if the
standard IEC summation rule is applied to the UPC
model. By adjusting the settings, the UPC model will
lead to results that are comparable to the IEC model,
as discussed in the next section.
3.2.3 Matching IEC and Equivalent UPC
Harmonic Current Model
After identifying the sources of discrepancies, the
following settings are proposed to improve the match
between the IEC model and the UPC model:
The in-phase UPC model needs to be set as
follows: the three-phase angles (i.e. 𝜑
, 𝜑
and 𝜑
) of positive-sequence and triplen
orders in UPC model are set to , −120° and
120°, while , 120° and −120° are used for
negative-sequence orders. The use of such in-
phase UPC harmonic source model will not
consider harmonic cancellation effect and will
ensure that the same amount of harmonic
current injections is obtained when multiple
Modelling Renewable Energy Sources for Harmonic Assessments in DIgSILENT PowerFactory: Comparison of Different Approaches
137
Table 7: THD results for self-defined IEC and in-phase
UPC modes under different study cases when using Yg-yg
transformers.
Three harmonic sources
Self-defined IEC
Model
In-Phase UPC Model
Bus
Case
4,5,6
(%)
Case
4
*,5*,6*
(%)
Case
4,5,6*
(%)
Case 6
3-Ph
(%)
B1 0.160 0.158
0.158 0.160
B2 0.620 0.613 0.613 0.620
B3 0.611 0.600 0.600 0.611
B4 0.698 0.690 0.690 0.698
B5 0.753 0.740 0.740 0.753
B6 0.745 0.732 0.732 0.745
B7 3.437 3.261 3.261 3.437
B8 0.753 0.740 0.740 0.753
B9 0.745 0.732 0.732 0.745
Seven harmonic sources
Self-defined IEC
Model
In-Phase UPC Model
Bus
Case
4,5,6
(%)
Case
4&6*
(%)
Case
5
(%)
Case 6
3-Ph
(%)
B1 0.257 0.243 0.243 0.248
B2
1.001
0.918 0.918 0.931
B3
1.008
0.934 0.935 0.960
B4
1.110
0.987 0.986 1.005
B5
1.166
0.998 1.000 1.030
B6
1.176
1.015 1.016 1.044
B7
3.647
3.196 3.201 3.391
B8
1.328
1.028 1.028 1.114
B9
1.371
1.046 1.046 1.172
Note the cases with ‘*’ label refer to the triplen harmonics are not
considered.
harmonic sources are connected to same
busbar (i.e. similarly to the IEC model
assessed by self-define IEC summation rule).
The magnitude of the harmonic currents in the
UPC model is required to be set to a negative
value when modelling a load element.
The Yg-yg transformer connection is needed
to avoid discrepancies at low-voltage busbars.
For example, different three-phase THD
values of UPC model for Case 6, and different
THDs of IEC and UPC models obtained from
different harmonic load flow solvers, as
discussed in 3.2.1
By using the settings above for the three harmonic
sources test, using the self-defined IEC and in-phase
UPC models lead to the same harmonic current
injection propagating to the upstream network. As
shown in Table 7 (bold values), the THDs obtained
from using in-phase UPC model are same to the self-
defined IEC model, except the UPC model under
Case 4 and 5 (because these cases are ignoring the
triplen harmonics). When triplen harmonics were
Table 8: THDs of self-defined IEC and in-phase UPC
models for different cases when length of transmission lines
and phase-shift of transformers are set to zero and using Yg-
yg transformers (seven harmonic sources).
Self-defined
IEC Model
In-Phase UPC
Model*
In-Phase UPC
Model
Bus
Case
4,5,6
(
%
)
Case
4,5,6
*
(%)
Case 6
3-Ph
(%)
Case
4,5,6
*
(%)
Case 6
3-Ph (%)
B1 0.387 0.368 0.387 0.366 0.387
B2 1.518 1.444 1.518 1.439 1.518
B3 1.518 1.444 1.518 1.439 1.518
B4 1.518 1.444 1.518 1.439 1.518
B5 1.518 1.444 1.518 1.439 1.518
B6 1.518 1.444 1.518 1.439 1.518
B7 4.974 4.748 4.974 4.708 4.974
B8 1.854 1.723 1.854 1.719 1.854
B9 1.992 1.813 1.992 1.808 1.992
‘In-phase UPC model*’ means the UPC model is assessed by self-
defined summation rule, and the ‘6*’ is the case 6 without
considering triplen harmonics.
ignored in the IEC models, the THDs were same to
the UPC model under different cases (see Table 7).
When seven harmonic sources 3 loads, 2 PVs
and 2 WTGs – located at different busbars were
considered, the THD values of self-defined IEC and
in-phase UPC model were not matching although the
differences were small (see Table 7). Note that the
THDs of in-phase UPC model under Case 5 were not
exactly the same as in Case 4 and Case 6*, because
the solver in Case 5 considers positive-sequence
impedance for all harmonic orders.
Nevertheless, it is possible to match the results
obtained from the IEC model with the self-defined
summation exponent (i.e. 1 for all frequencies) by
using the proposed in-phase model if the length of the
transmission lines and the phase-shift of the
transformers are considered to be zero. In this way,
the diversity due to the network impedance is not
considered, therefore the comparison between
different harmonic modelling approaches and
harmonic load flow solvers is straightforward. The
voltage THD results in Table 8 show that the use of
in-phase UPC model produce the same THDs (the
bold values) as the use of self-defined IEC model for
Case 6 under the specified system conditions.
Moreover, Table 8 shows that the UPC model
assessed by IEC summation rule with self-defined
summation exponent (i.e. In-Phase UPC*’) is able to
produce the same result for Case 6 (see bold values in
Table 8). The differences between In-Phase UPC and
In-Phase UPC under Case 4, 5 and 6* are because the
device L3 in the case In-Phase UPC* was using IEC
model that takes triplen harmonics into account.
Based on the results above, even with the
proposed settings, the in-phase UPC model does not
allow exact match of the IEC model results obtained
by applying the standard summation rule when
SIMULTECH 2021 - 11th International Conference on Simulation and Modeling Methodologies, Technologies and Applications
138
multiple harmonic sources are located at different
busbars. This is because the UPC model takes into
account the cancellation caused by the network
impedance (i.e. superposition law): more specifically,
it was found that the harmonics propagating to the
network through the transmission lines and phase-
shifting transformers result in harmonic phase shift
when using the UPC model. On the contrary, the
standard IEC model summation rule accounts for the
effect of harmonic cancellation from the harmonic
source injections and the effect of network impedance,
irrespective of the transformer phase shift.
4 CONCLUSIONS
This paper addressed different approaches in
modelling unbalanced systems with large penetration
of RESs for the purpose of harmonic studies. Two
aspects were considered: frequency scans and
harmonic penetration studies.
The frequency scans indicated that the single-
phase and three-phase network impedance
characteristics were not affected by the harmonic
models and the number of harmonic sources, as well
as the use of balanced and unbalanced solver.
Various harmonic settings in DPF were tested to
solve harmonic power flow using the IEC and UPC
model. the discrepancies caused by the two models
and harmonic load flow solvers have been analysed
and clarified by comparing different cases. In
addition, the possibility and requirement of modelling
equivalent IEC model by using the UPC model have
been proposed and verified.
Finally, it was concluded that the UPC model and
the unbalanced harmonic load flow should be
considered for harmonic analysis for certain
operating conditions, for example (1) in stochastic
harmonic analysis, (2) where it is deemed that the
generic IEC summation rule may lead to
underestimation or overestimation of harmonic
levels, as it assumes a ‘standard’ cancellation of
harmonic that may not take place in the practice.
When power converter-based devices, such as RESs,
are considered, it is recommended to adopt the UPC
model that accurately considers harmonic magnitude
and phase. In this way, the harmonic cancellation
effect is considered properly, and thus the harmonic
assessment is more accurate and reliable.
Future work will include: developing a frequency-
dependent Norton admittance model to be used with
the UPC harmonic current source; applying this
model to a larger network representing a portion of
the UK transmission grid and studying increasing
levels of RESs and their impact on harmonic levels
on the system.
ACKNOWLEDGEMENTS
The authors acknowledge the support of the UK
Engineering and Physical Sciences Research Council
(EPSRC); Project EP/T013206/1.
REFERENCES
Ambrož, B., Boštjan, B., Aljaž, Š., Mari, L., Jako, K., &
Kai, S. (2017). Simulation Models for Power-Quality
Studies in Power-Electronics Rich Power Networks-
Deliverable 5.2. MIGRATE – Massive InteGRATion of
Power Electronic Devices, 1–323.
Bećirović, E., Jovica, V. M., Simon, H., Maren, K., Kai, S.,
& Dejan, M. (2018). Propagation of PQ disturbances
Through The Power Networks - Deliverable 5.3.
MIGRATE – Massive InteGRATion of Power
Electronic Devices, 1–154.
Cherian, E., Bindu, G. R., & Chandramohanan, P. S.
(2016). Pollution Impact of Residential Loads on
Distribution System and Prospects of DC Distribution.
Engineering Science and Technology, an International
Journal, 19(4), 1655–1660.
DIgSILENT. (2020a). PowerFactory 2020.
https://www.digsilent.de/en/powerfactory.html
DIgSILENT. (2020b). PowerFactory 2020 User Manual.
889–906. https://www.digsilent.de/en/powerfactory.
html
Elkholy, A. (2019). Harmonics Assessment and
Mathematical Modeling of Power Quality Parameters
for Low Voltage Grid Connected Photovoltaic Systems.
Solar Energy, 183, 315–326.
Eltouki, M., Rasmussen, T. W., Guest, E., Shuai, L., &
Kocewiak, Ł. (2018). Analysis of Harmonic
Summation in Wind Power Plants Based on Harmonic
Phase Modelling and Measurements. 17th International
Wind Integration Workshop, 1–7.
Energy Networks Association. (2020). Harmonic Voltage
Distortion and the Connection of Non-Linear and
Resonant Plant and Equipment to Transmission
Systems and Distribution Networks in the United
Kingdom. ENA Engineering Recommendation G5, 5.
Energyiforsk. (2018). Harmonics and Wind Power. Daphne
Schwanz, Math Bollen, Lulea University of Technology,
1–42.
Erik, J., & Leigh, S. H. (2016). Power Quality Assessment
of Solar Photovoltaic Inverters. Sustainable
Technologies Evaluation Program, Toronto and
Region Conservation Authority, Toronto, Ontario, 1–
58.
Ghassemi, F., & Koo, K. (2010). Equivalent Network for
Wind Farm Harmonic Assessments. IEEE Transactions
on Power Delivery, 25(3), 1808–1815.
Modelling Renewable Energy Sources for Harmonic Assessments in DIgSILENT PowerFactory: Comparison of Different Approaches
139
Herraiz, S., Sainz, L., & Clua, J. (2003). Review of
Harmonic Load Flow Formulations. IEEE Transactions
on Power Delivery, 18(3), 1079–1087.
IEC TR 61000-3-6. (2008). Electromagnetic Compatibility,
Limits – Assessment of Emission Limits for The
Connection of Distorting Installations to MV, HV and
EHV Power Systems.
IEEE Power and Energy Society. (2014). IEEE
Recommended Practice and Requirements for
Harmonic Control in Electric Power Systems. IEEE
Std. 519-2014.
Jensen, C. F. (2018). Harmonic Background Amplification
in Long Asymmetrical High Voltage Cable Systems.
Electric Power Systems Research, 160, 292–299.
Koo, K. L., & Emin, Z. (2016). Comparative Evaluation of
Power Quality Modelling Approaches for Offshore
Wind Farms. 5th IET International Conference on
Renewable Power Generation (RPG), 1–7.
Medina, A., Segundo, J., Ribeiro, P., Xu, W., Lian, K. L.,
Chang, G. W., Dinavahi, V., & Watson, N. R. (2013).
Harmonic Analysis in Frequency and Time Domain.
IEEE Transactions on Power Delivery, 28(3), 1813–
1821.
Mendonça, G. A., Pereira, H. A., & Silva, S. R. (2012).
Wind Farm and System Modelling Evaluation in
Harmonic Propagation Studies. Renewable Energy and
Power Quality Journal, 1(10), 647–652.
National Grid ESO. (2019). Future Energy Scenarios 2019.
http://fes.nationalgrid.com/fes-document/
Oliver, A., Liam, M., Griffiths, F., Shafiu, A., & Forooz, G.
(2018). Subgroup Report – Harmonics Above 50th.
ENA Engineering Recommendation G5.
Preciado, V., Madrigal, M., Muljadi, E., & Gevorgian, V.
(2015). Harmonics in A Wind Power Plant. IEEE
Power and Energy Society General Meeting, 1–5.
Preda, T. N., Uhlen, K., & Nordgard, D. E. (2012).
Instantaneous Harmonics Compensation Using Shunt
Active Filters in A Norwegian Distribution Power
System With Large Amount of Distributed Generation.
3rd IEEE International Symposium on Power
Electronics for Distributed Generation Systems
(PEDG), 153–160.
Rampinelli, G. A., Gasparin, F. P., Bühler, A. J.,
Krenzinger, A., & Chenlo Romero, F. (2015).
Assessment and Mathematical Modeling of Energy
Quality Parameters of Grid Connected Photovoltaic
Inverters. Renewable and Sustainable Energy Reviews,
52, 133–141.
Rauma, K. (2012). Electrical Resonances and Harmonics in
a Wind Power Plant. In Aalto University School of
Electrical Engineering Kalle.
Robinson, D. (2003). Harmonic Management in MV
Distribution Systems. University of Wollongong.
Working Group JWC-C4/B4.38. (2019). Network
Modelling for Harmonic Studies. CIGRE, 1–241.
Working Group JWG-C4/C6.29. (2016). Power Quality
Aspects of Solar Power. CIGRE, 1–109.
SIMULTECH 2021 - 11th International Conference on Simulation and Modeling Methodologies, Technologies and Applications
140