Parametric Analysis of Greenhouse Gas Emissions of the Technical
Building System Alternatives in Detached Houses Retrofitted to
nZEB Level
László Zsolt Gergely
a,*
, and Tamás Csoknyai
b
Budapest University of Technology and Economics, Faculty of Mechanical Engineering, Department of Building Services
and Process Engineering, Műegyetem rkp. 3, Budapest 1111, Hungary
Keywords: nZEB, Near zero energy buildings, Climate change, Carbon footprint, Heat pump, Total equivalent warming
impact
Abstract: Buildings account for a significant part of greenhouse gas emissions. A reasonable way of mitigation is the
retrofit of the building stock, both from the perspective of the building envelope and the technical building
system. However, to maximize carbon emission savings, effects of these two measures shall be observed hand
in hand. This paper approaches the issue through the possible renovation of the detached houses of the
Hungarian residential building stock to a nearly zero energy building (NZEB) level. Three system layouts,
namely air-to-water heat pumps, air-to-air heat pumps with electric boilers and gas condensing boilers are
compared in terms of greenhouse gas emissions while covering heating and domestic hot water demands.
Results reflect that heat pumps offer the possibility of a remarkable reduction of carbon-dioxide emissions
compared to condensing gas boilers in case of the present electricity mix of Hungary. Furthermore, it appears
that after the NZEB renovation, air-to-water heat pumps represent the best solution for detached houses. In
the meanwhile, air-to-air heat pumps with electric boilers could remain eco-friendly for applications with
relatively low hot water needs.
1 INTRODUCTION
Buildings account for a significant part of both
primary energy consumption and carbon emissions
worldwide (Mayer, Szilágyi, and Gróf 2020). As a
result, building sector is often prioritised in policies
aiming the reduction of energy consumption and
greenhouse gas emissions. Performance requirements
of building structures and technical building systems
are getting more and more strict, which in Europe can
be traced trough Nearly Zero Energy Building
(NZEB) requirements, targeting both minimizing the
energy consumption and enhancing the use of
renewable energy sources (Balint & Kazmi, 2019).
For the latter, heat pumps are often considered as a
widely available and effective solution of renewable
based technical building system (Marinelli et al.,
2019).
a
https://orcid.org/0000-0001-9365-211X
b
https://orcid.org/ 0000-0003-0327-0316
Nevertheless, there are other factors to consider
besides energy consumption to estimate greenhouse
gas emissions of a system. Several calculation
methods aim to include such indicators. In case of
heat pumps the Total Equivalent Warming Impact
(TEWI) is widely used (Mota-Babiloni et al., 2020).
Despite the fact that both NZEB regulations and
TEWI calculations are widely known, they are rarely
observed together. This paper introduces and
calculates parameters to define the best performing
technical building system out of three up-to-date
layouts, namely gas condensing boiler, air-to-water
heat pump (AWHP) and air-to-air (AA) heat pump
with electric boiler for hot water generation. Section
2 reveals the parameters of the study, and that of the
carbon footprints (CF) of the three technical building
systems. Section 3 first presents the emission
calculations of the different systems for the specific
cases, then reveals the certain parameters, where air-
source heat pump-based systems perform better than
Gergely, L. and Csoknyai, T.
Parametric Analysis of Greenhouse Gas Emissions of the Technical Building System Alternatives in Detached Houses Retrofitted to nZEB Level.
In Proceedings of the 7th International Conference on Water Resource and Environment (WRE 2021), pages 231-239
ISBN: 978-989-758-560-9; ISSN: 1755-1315
Copyright
c
2022 by SCITEPRESS – Science and Technology Publications, Lda. All rights reserved
231
the gas condensing boiler system. This is continued
with contrasting the air-source heat pump-based
systems. Finally, section 4 concludes the results.
2 PARAMETERS OF THE STUDY
2.1 Buildings Under Study
From the perspective of greenhouse gas emission,
residential sector of buildings is often considered a
more significant emitter than commercial sector (Ge
& Friedrich, 2020). In this paper therefore we
approach the problem from the residential buildings’
perspective. Data of the Hungarian building stock
was used, containing 19 types of residential buildings
to describe the national typology (Tamas, 2013), out
of which 9 types of detached houses (each named by
the reference typology) were considered as potential
sites for heat pump application. In terms of
construction date, selected types fall in the period
from the 1950’s to today’s constructions. In case of
the newest types, the original construction itself
guarantees NZEB parameters, for the former ones
NZEB retrofit actions are considered.
In this paper by NZEB-level buildings we assume
buildings with a building shell fulfilling NZEB
requirements, not considering if they fulfil additional
requirements, such as overall energy performance and
renewable energy share.
Figure 1: Typical meteorological year of Budapest, Hungary, generated from the data of years 2007-2016 (Poggi et al., 2008).
2.1.1 Energy Needs and Heat Loads
Hungary, located in central Europe, has a temperate
seasonal climate. In these circumstances, the role of
the technical building system is usually to cover the
heating and domestic hot water needs of the houses.
Cooling needs are relatively low due to the climatic
characteristics and the national building code (TNM
7/2006 Decree) regarding NZEB buildings, aiming to
minimize or even exclude active cooling in case of
the residential sector, with proper building design
(Ministry Without Portfolio of Hungary, 2020).
Having a look at Figure 1, representing a typical
meteorological year (TMY) of Budapest (European
Commission, 2017), it is seen that for a significant
part of the year the average external temperature by
day is below under 12°C, which is usually considered
as the heating threshold temperature.
On the other hand, the number of days with the
average above 23°C (which is determined as a cooling
threshold temperature with a maximum internal
temperature of 26°C and subtracting the maximum
allowed overheating temperature difference of 3°C) is
much fewer. Considering occupancy schedule as well,
it is seen that the number of hours where the external
temperature is above 26°C in the period of 17:00
07:00 is only 18 hours a year. For the present study
cooling, therefore, is not considered.
The design heat load for heating is determined
according to the national building code (Ministry
Without Portfolio of Hungary, 2020), as well as the
net energy needs of heating and DHW production.
DHW net energy need is determined as 30
kWhth/m
2
year, therefore is the same before and after
the building reconstructions. On the contrary, net
energy needed for heating, calculated with an internal
temperature of 20°C, reduces significantly with
NZEB level refurbishment. For the various types of
buildings, decrease of the sum of the net energy needs
comes with different extent but in general for building
types 1-5, demand after reconstruction is
approximately the third to fourth of the original state,
while in case of types 6 and 7 it is 70%.
Table 2
reveals, that the extent of it is highly influenced by
‐10
‐5
0
5
10
15
20
25
30
1 21 41 61 81 101 121 141 161 181 201 221 241 261 281 301 321 341 361
Temperature[°C]
DayofTMY(2007‐2016)
Avg.externaltemperaturebyday 23°C 12°C
WRE 2021 - The International Conference on Water Resource and Environment
232
the ratio of 𝑄

and 𝑄
, as only the latter changes
by the retrofit.
2.2 Appliances
Two types of air-source heat pumps were considered
in the calculations, as their application comes with a
lower limit in terms of the source side, compared to
ground-source or water-source heat pumps. One type
is the air-to-water heat pump that itself can cover both
heating and DHW net energy needs.
The other air-source heat pump type is air-to-air
heat pump. For DHW generation electric boilers are
assumed. As a reference, emissions of gas condensing
boiler systems are calculated as well. Carbon
footprint of the listed systems are calculated in the
followings.
2.2.1 TEWI of Heat Pump Systems
For the heat pump systems, TEWI calculations are
used to approximate the greenhouse gas emissions for
the lifetime of the appliance. TEWI considers two
types of emissions. Direct emissions are related to the
refrigerant used in the heat pump (described with the
first two terms of equation 1), while indirect
emissions are corresponding to the electricity used by
the heat pump (described with the third term) (Mota-
Babiloni et al., 2020).
𝑇𝐸𝑊𝐼
𝐺𝑊𝑃 ∗ 𝑚 ∗ 𝐿

∗𝑛
𝐺𝑊𝑃 ∗ 𝑚
1𝛼

𝐸

∗𝛽
∗𝑛
(1)
In TEWI, 𝐺𝑊𝑃 stands for the Global Warming
Potential (kgCO
2
eq./kg), 𝑚 (kg) represents the mass
of the refrigerant charge. 𝐿

(% / year) is the
annual loss of refrigerant charge through leakages and
𝛼

(%) stands for the amount of charge that can be
potentially recovered at the end of life. Factor 𝑛
(years) appearing is the estimated lifespan of the heat
pump.
The indirect emissions part is characterised with
𝐸

(kWh
e
/year), annual electricity consumption,
multiplied with the lifespan and applying the carbon
intensity factor 𝛽
(kgCO
2
eq./kWh
e
) of the
electricity, that describes the greenhouse gas
emissions that the generation of 1 kWh
e
of power is
accounted for.
2.2.2 Parameters of TEWI Calculation
In practice, TEWI is calculated for the heat pump that
is subject of the specific calculation. However, to
draw conclusions about the emissions of the different
heat pump-based systems under various conditions,
generalization of these values is necessary. In case of
the refrigerant parameters, and therefore the GWP
value, it is reasonable to define a type of refrigerant
for the study that is widely used. For that reason,
refrigerant R32 is taken into consideration, with a
global warming potential of 675 kgCO2eq./kg (Choi
et al., 2017).
The mass of the charge, though, is also dependant
on the specification of the heat pump and is in
accordance with the capacity of the appliance.
Usually, the specific charge mass is between 0.24 – 1
kg/kW (Poggi et al., 2008). In the study, 0.3 kg/kW is
used, just as applied in (Johnson, 2011). Leakage
rates vary on a wide scale in different studies,
however it is believed that they have a modest effect
on the results (Johnson, 2011). In case of the annual
leakage rate the value is usually around 6% (Greening
& Azapagic, 2012; Johnson, 2011). For recovery rate
also many different values can be found in literature.
Calculations of this paper assume 80% of recovery
rate, which is quite general (Greening & Azapagic,
2012). The expected lifespan of the appliances in the
following calculations is 15 year (Mota-Babiloni et
al., 2020).
Carbon intensity factor in TEWI is an average
value for the electricity used throughout the lifetime.
However, when calculating in advance, only
estimations could be used. Though carbon intensity is
believed to continuously decrease in the future, in this
study, carbon intensity of the installation year is used
through the lifetime, to rather err on the side of
caution.
2.2.3 Energy Consumption of the Heat
Pumps
It is often highlighted that the dominating part of
greenhouse gas emissions is the indirect part of
TEWI, energy consumption related parameters
(Greening & Azapagic, 2012; Mota-Babiloni et al.,
2020). Annual electricity consumption of this term
can be determined various ways. The most precise
would be measuring the consumption, however the
carbon emission estimation is carried out in advance,
therefore it is not possible in our case. Another option
could be a detailed dynamic modelling of the heat
pumps performance for the specific cases, which is
resource and time demanding. A simpler, though for
Parametric Analysis of Greenhouse Gas Emissions of the Technical Building System Alternatives in Detached Houses Retrofitted to nZEB
Level
233
annual calculations still sufficiently appropriate
option is estimating the consumptions with the
Seasonal Coefficient of Performance (SCOP) of the
heat pumps (Huang & Mauerhofer, 2016), that is
applied further on in the paper. 𝐸

is therefore
determined as the ratio of the net energy need of
heating (𝑄
), net energy need of DHW production
(𝑄

) and the specific SCOP.
In case of the AWHP this approach is used for
estimating the electricity consumption of heating and
DHW production, and in case of air-to-air heat pump
to determine electricity consumption of heating.
SCOP values are considered according to the guide of
the Danish Energy Agency for these cases
(Energistyrelsen, 2018).
In case of the air-to-water heat pump, the annual
energy consumption 𝐸
,
appears as:
𝐸
,
𝑄
𝑆𝐶𝑂𝑃
,
𝑄

𝑆𝐶𝑂𝑃
,
(2)
where 𝑆𝐶𝑂𝑃
,
stands for the seasonal coefficient
of performance of heating with AWHP and similarly,
𝑆𝐶𝑂𝑃
,
is for the characterization of the
efficiency of DHW production with AWHP.
Electricity consumption of heating with air-to-air heat
pump, 𝐸
,
is expressed with the denominator of
𝑆𝐶𝑂𝑃
,
that stands for the seasonal coefficient of
performance of heating. The electricity consumption
of DHW production in case of an electric boiler (EB)
is estimated similarly, with using of the efficiency of
the boiler, η

that is considered 100% in the
calculations. The annual electricity consumption of
the air-to-air heat pump-based system is denoted with
𝐸
,
𝐸
,
.
𝐸
,
𝐸
,
𝑄
𝑆𝐶𝑂𝑃
,
𝑄

η

(3)
The carbon intensity factor also has a high impact
on the results. For this reason, this value should
consider future trends in power generation and
geographic location. In this study, yearly averages of
the present (the same as for the year 2020), 2030 and
2050 electricity mix are considered for the Hungarian
electricity grid (Kiss, Kácsor, and Szalay 2020).
2.2.4 Carbon Footprint of the ASHP-based
Systems
Knowing the energy consumption of the ASHP based
systems, CF of the systems can be expressed. In case
of air-to-water heat pump TEWI and the carbon
footprint of the system equal:
𝐶𝐹

𝑇𝐸𝑊𝐼

𝐺𝑊𝑃 ∗ 𝑚 ∗ 𝐿

∗𝑛
𝐺𝑊𝑃 ∗ 𝑚 ∗
1𝛼

𝐸
,
∗𝛽
𝑛
(4)
For further calculations notation 𝐷 is introduced
for the direct emission part.
𝐶𝐹

𝐷
𝐸
,
∗𝛽
𝑛
In case of the air-to-air heat pump-based system,
TEWI, however, would only represent the emissions
related to heating with the air-to-air heat pump, but
not the DHW generation with the electric boiler. For
that reason, GHG emission of the electric boiler is
approximated with the electricity consumption of the
boiler and the carbon intensity factor of the grid.
Production phase is neglected (just like in TEWI in
case of the heat pumps). As a result, CF of this system
can be expressed as:
𝐶𝐹
&
𝐷
𝐸
,
𝐸
,
∗𝛽
∗𝑛
(5)
Assuming the same leakage rates, charge capacity
and refrigerant type, direct emissions ( 𝐷 of the
different heat pump systems are considered equal.
2.2.5 Gas Condensing Boiler Emissions
Emissions of the condensing boiler are used as a
reference case, to allow distinguishing the effect of
the NZEB construction and the selection of heat
pumps for technical building system. Greenhouse gas
emissions of the gas condensing boiler system are
calculated with the help of Ecoinvent database, that is
a widely used database for LCAs (Ecoinvent, 2014).
Based on that, a carbon intensity factor, 𝛽

is
introduced to determine the carbon emissions of the
natural gas condensing boiler as
𝐶𝐹

𝛽

∗𝐸
,
∗𝑛
(6)
where 𝐶𝐹

(kgCO2eq) refers to the carbon footprint
of the heat generation with gas condensing boiler,
𝐸
,
is the final energy consumption of the gas
condensing boiler, which, similarly to the other
appliances is the sum of energy needed for heating
and DHW production divided by the efficiency of the
boiler, η

, that is considered 95% in the
calculations
.
WRE 2021 - The International Conference on Water Resource and Environment
234
2.2.6 Sizing the Appliances
As greenhouse gas emissions are dependent on the
size of the heat pump (through the introduced scaling
factor for the refrigerant charge amount), capacity of
the different appliances should be determined. In our
research we assumed the capacity of the heat pumps
according to the heat load of the analysed buildings.
In case of the AWHP it is presumed that this
capacity is sufficient for covering the DHW needs as
well. When electric boiler is used for DHW
generation, the capacity of the equipment is irrelevant,
as in this case, only electricity used has impact on
carbon emissions, production of the equipment is
excluded from CF calculation (as suggested in section
2.2.4,). sums up all the parameters of the technical
building systems used in the study.
Table 1: Values used is Carbon Footprint calculations of the technical building system.
3 RESULTS AND DISCUSSION
3.1 Carbon Emissions for the Different
Technical Building Systems
In case of the gas condensing boiler system, carbon
dioxide emissions are directly proportional to the
energy needs of the specific cases, as heating and
DHW production are not distinguished from this
perspective (equation 6). It provides a representation
of a technical building system that is though up-to-
date, comes with a limit in terms of reducing GHG
emissions as lacks the integration of renewable
energy sources.
In Figure 2, it is recognisable, that the gas boiler
system represents larger emissions than the ASHP
based systems, even with the electricity mix of 0.1234
kgCO2eq./kWh
e
, that is suggested by a study as the
carbon intensity factor of the 2020 electricity mix of
Hungary (Kiss, Kácsor, and Szalay 2020).
It is also notable that the amount of carbon
emissions saved with NZEB reconstruction of the
buildings and of the technical building systems with
ASHPs is the same orders of magnitude (applying the
2020 electricity mix).
Potential emission savings, however, are pushed
even further with the future electricity mixes of 2030
and 2050 as seen in Figure 3. As more and more
renewables are foreseen to be integrated in power
production, carbon intensity factor of the power grid
𝛽
gradually reduces from 0.3769 kgCO
2
eq./kWh
e
of 2020 to somewhere around 0.1234 and 0.0637
kgCO
2
eq./kWh
e
by the years 2030 and 2050
respectively, as a study reveals (Kiss, Kácsor, and
Szalay 2020).
3.2 Determining the Best Performing
Equipment for an Application
Carbon intensity factor of the electricity consumed by
the appliances is an important factor of GHG
Name Symbol Value Unit
Global Warming Potential of refrigerant R32 𝐺𝑊𝑃 675 kgCO
2
eq./kg
mass of refrigerant charge 𝑚
0.3 kg/kW * capacity of
the ASHP
kg
annual leakage rate of charge 𝐿

6 %/year
estimated lifespan 𝑛 15 years
recovered refrigerant amount at end-of-life 𝛼

80 %
carbon intensity factor of the Hungarian power
grid for 2020, 2030 and 2050 respectively
𝛽
0.3769
0.1234
0.0637
kgCO
2
eq./kWh
e
SCOP of air-to-water HP, DHW production 𝑆𝐶𝑂𝑃
,
3.35
kW/kW
SCOP of air-to-water HP, heat production 𝑆𝐶𝑂𝑃
,
3.55
SCOP of air-to-air HP, heat production 𝑆𝐶𝑂𝑃
,
4.9
natural gas burning factor 𝛽

248.6 gCO
2
/kWh
th
gas-condensing boiler efficiency
η

95 %
electric boiler efficiency
η

100 %
Parametric Analysis of Greenhouse Gas Emissions of the Technical Building System Alternatives in Detached Houses Retrofitted to nZEB
Level
235
emissions and as a result also plays a decisive role
when it comes to the selection of the system with the
lowest carbon equivalent. Noting that ASHP systems
appeared with less carbon emissions for all the cases,
brings up the question of the conditions where
condensing gas boiler technology could result better
emission values.
Figure 2: Carbon Footprint of the different technical building systems of the Hungarian detached houses, before and after
NZEB-level reconstruction, considering the 2020 carbon intensity factor for the lifetime.
Figure 3: Carbon Footprint of the ASHP based technical building systems of the Hungarian detached houses after NZEB-
level reconstruction, considering the 2020, 2030 and 2050 carbon intensity factors.
3.2.1 Comparing ASHP Systems with Gas
Condensing Boilers
Both ASHP based technologies are compared with
the gas condensing boiler system. For that, equations
(4,5,6) describing the CF of the different systems are
examined. Comparing the ASHP based systems with
the condensing boiler system it is remarkable, that
from the perspective of the equipment only the carbon
intensity factor 𝛽
represents a variable as other
values are set by the specifications of the appliances (
and the energy needs of the cases (Table 2). This
allows to express the equations to the carbon intensity
factor, that represents a threshold for the ASHP based
technical building systems, when compared to the gas
condensing boilers. Carbon intensity values above
this threshold would mean that gas condensing boilers
are preferred, below this carbon intensity ASHP
based systems would result less carbon dioxide
emissions for the lifetime of the technical building
WRE 2021 - The International Conference on Water Resource and Environment
236
system. Mathematically, this is expressed with
equality between (4) and (6), rearranged to express
the carbon intensity, that comes as follows:
𝛽
,,
𝛽

∗𝐸
,
∗𝑛𝐷
1
𝐸
,
∗𝑛
(7)
where 𝛽
,,
represents the carbon intensity which
would result the same carbon-dioxide emissions for
the AWHP system and the gas condensing boiler
system. For the 9 building types observed, this
𝛽
,,
varies around the value of 0.9
kgCO2eq./kWh
e
, seen in Table 2. As the carbon
intensity of the Hungarian electricity mix is notably
lower than this, AWHP provides a better choice than
gas condensing boiler for all the observed residential
detached houses.
The case of air-to-air heat pump-based system is
similar. Direct emission part of TEWI equals with the
AWHP system’s. However, the indirect part differs as
electricity consumption of the air-to-air heat pump
and of the electric boiler are both included. Carbon
intensity factor to decide whether condensing boiler
or air-to-air heat pump, combined with electric boiler
performs better is expressed as follows (after
rearranging the equality of (5) and (6)).
𝛽
,
&
,
𝛽

∗𝐸
,
∗𝑛𝐷
𝐸
,
𝐸
,
∗𝑛
(8)
𝛽
,&,
values appear on a much wider range
than that of 𝛽
,,
, from 0.963 kgCO2eq./kWh
e
to
as low as 0.462 kgCO2eq./kWh
e
, for types 1 and 7
respectively (seen in Table 2).
As only energy consumption of the appliances
change, compared to the previous case, the reason for
the alteration of the values has to be in reliance with
that. It is notable, that the greater the ratio of the net
energy demand of DHW production 𝑄

and
heating 𝑄
is, the higher the emissions of the
ASHP based systems will be, as DHW production
comes with lower efficiency for both ASHP based
systems. Furthermore, in case of the electric boiler,
the efficiency of DHW generation ( η

is
significantly lower compared to the heat generation
with heat pump ( 𝑆𝐶𝑂𝑃
,
, resulting larger
alterations in 𝛽
,&,
.
This also explains why 𝛽
,,
varies in a
remarkably more moderate range. Seasonal
coefficient of performance of DHW production
(𝑆𝐶𝑂𝑃
,
) and space heating (𝑆𝐶𝑂𝑃
,
comes
with notably lower difference for that case.
Table 2 sums up the different carbon intensity
thresholds for the examined cases of the Hungarian
residential building stock. If the carbon intensity is
below the threshold of 𝛽
,,
and 𝛽
,&,
of
the specific cases, ASHP-based systems offer a more
favourable way of heating and domestic hot water
production, from the perspective of carbon emissions.
On the contrary, if carbon intensity factor exceeds
these thresholds, then condensing boilers are the
preferable.
Table 2: Carbon intensity limits and net energy need ratios for the different detached houses of the Hungarian building
typology with the 2020 carbon intensity.
Building type 1 2 3 4
Original NZEB Original NZEB Original NZEB Original NZEB
Heat load kW 8.97 2.35 12.13 3.37 8.87 2.41 15.96 3.17
Q
H
kWh
th
/year 20 132 4 707 28 433 7 116 19 780 5 007 36 282 7 148
Q
DHW
kWh
th
/year 1 680 1 680 2 727 2 727 1 782 1 782 3 294 3 294
𝛽
,

,

kgCO
2
eq./kWh
e
0.903 0.896 0.904 0.896 0.903 0.896 0.903 0.896
𝛽
,
&
,

kgCO
2
eq./kWh
e
0.963 0.620 0.935 0.604 0.947 0.621 0.946 0.565
Q
DHW
/Q
H
limit [-] 0.111
Q
DHW
/Q
H
[-] 0.083 0.357 0.096 0.383 0.090 0.356 0.091 0.461
Building type 5 6 7 16 17
Original NZEB Original NZEB Original NZEB New constr. NZEB
Heat load kW 9.06 2.70 6.14 2.08 5.84 3.36 5.98 3.35
Q
H
kWh
th
/year 20 702 3 529 12 144 7 405 12 028 7 409 12 431 7 378
Q
DHW
kWh
th
/year 2 748 2 748 2 853 2 853 3 174 3 174 3 525 3 525
𝛽
,

,

kgCO
2
eq./kWh
e
0.902 0.883 0.897 0.903 0.898 0.896 0.897 0.896
𝛽
,
&
,

kgCO
2
eq./kWh
e
0.861 0.462 0.719 0.608 0.691 0.580 0.674 0.557
Q
DHW
/Q
H
limit [-] 0.111
Q
DHW
/Q
H
[-] 0.133 0.779 0.235 0.385 0.264 0.428 0.284 0.478
Parametric Analysis of Greenhouse Gas Emissions of the Technical Building System Alternatives in Detached Houses Retrofitted to nZEB
Level
237
3.2.2 Selection between ASHP based
Systems
Comparing the ASHP based systems in Figure 2,
reveals that in most of the cases AWHP guarantees
better results. Although, there are certain conditions
where air-to-air heat pump with the electric boiler
prove to result lower emissions. It is notable that it
only appears for the original state and never for the
NZEB option. In case of these examples (building
types 1-4) the NZEB option leads to a technological
shift in the terms of the system with the lowest CF.
The equations only differ in the amount energy
consumed (as a result of the different efficiencies of
the specific equipment used). As for the observance,
the equality of CF of the ASHP based systems is
expressed for the ratio of the net energy needs (9).
This therefore defines the circumstances that results
in equal emissions for the systems. Above this ratio,
AWHP performs better as a result of more efficient
DHW production, below this ratio higher SCOP of
air-to-air heat pump makes the latter system a more
favourable choice.
𝑸
𝑫𝑯𝑾
𝑸
𝑯
𝑺𝑪𝑶𝑷
𝑯,𝑨𝑨
𝑺𝑪𝑶𝑷
𝑯,𝑨𝑾
𝑺𝑪𝑶𝑷
𝑯,𝑨𝑨
∗𝑺𝑪𝑶𝑷
𝑯,𝑨𝑾
𝑺𝑪𝑶𝑷
𝑫𝑯𝑾,𝑨𝑾
𝛈
𝒆𝒃
𝑺𝑪𝑶𝑷
𝑫𝑯𝑾
,
𝑨𝑾
𝛈
𝒆𝒃
(9)
The present efficiency values result in a ratio of
approximately 0.11 [-] of DHW net energy need and
the net energy needed for space heating (SH). For
building types 1-4 the same ratios are remarkably
lower for the original state, represented in Table 2,
which can be explained with the significant decrease
of space heating demand as a result of the NZEB
retrofit, while the DHW demand remains the same.
As seen, the ratio of the net energy consumption
(of types 1-4) prior to the renovation is below the
threshold limit of 0.11, while after the renovation is
above. This explains why air-to-air heat pumps with
electric boilers emit less carbon dioxide before the
retrofit, and AWHPs after the NZEB retrofit. The
technological swift can be traced in Figure 2.
4 CONCLUSIONS AND
OUTLOOK
In this paper three technical building systems were
compared to reveal the conditions where a specific
system could minimize carbon dioxide emissions.
Comparison of carbon footprints justified that heat
pump-based systems could provide lower emissions
compared to gas condensing boiler system. However,
there could be certain applications, with high carbon
intensity factors, where the latter is still preferable. In
comparison with AWHP, this limit is high, about 0.9
kgCO2eq./kWh
e
. Comparing with air-to-air heat
pump and electric boiler, the limit could appear even
as low as 0.462 kgCO2eq./kWh
e
in case of the
Hungarian residential building stock. The
significance of the DHW-to-SH demand ratio of the
houses is also highlighted when heat pump-based
building technical systems are compared to
condensing boiler technology.
When comparing the air-source heat pump-based
systems it can be concluded that in contrast only the
DHW-to-SH demand ratio matters. The threshold of
this net energy need
ratio is low, around 0.11,
meaning that for residential NZEBs air-to-water heat
pumps are more favourable. Nevertheless, under
certain circumstances, for instance in case of building
functions with low domestic hot water
demand,
resulting in a lower ratio, air-to-air heat pumps with
electric boilers could be preferable.
Results of the study could be essential for
environmentally conscious decision-making in
legislation on a building cluster level. However, it
should be highlighted that the presence of significant
cooling needs could modify the threshold of the net
energy ratios, therefore further research is needed to
extend the parameters with the presence of cooling
needs.
ACKNOWLEDGEMENTS
The work has been carried out at BME within the
research project entitled “Large Scale Smart Meter
Data Assessment for Energy Benchmarking and
Occupant Behavior Profile Development of Building
Clusters”. The project (no. K 128199) has been
implemented with the support provided from the
National Research, Development and Innovation
Fund of Hungary, financed under the K_18 funding
scheme.
The research has also been supported by the NRDI
Fund (TKP2020 IES, Grant No. BME-IE-MI) based
on the charter of bolster issued by the NRDI Office
under the auspices of the Ministry for Innovation and
Technology.
WRE 2021 - The International Conference on Water Resource and Environment
238
REFERENCES
Balint, A., & Kazmi, H. (2019). Determinants of Energy
Flexibility in Residential Hot Water Systems. Energy
and Buildings, 188–189, 286–96.
Choi, S. Y., Oh, J. W., Hwang, Y. H., & Lee, H. S. (2017).
Life Cycle Climate Performance Evaluation (LCCP) on
Cooling and Heating Systems in South Korea. Applied
Thermal Engineering, 120, 88–98.
Ecoinvent. (2014). Ecoinvent 3.4. www.ecoinvent.com.
Energistyrelsen. (2018). Technology Data for Heating
Installations.
European Commission. (2017). JRC Photovoltaic
Geographical Information System (PVGIS) - European
Commission. Photovoltaic Geographical Information
System: 1.
https://re.jrc.ec.europa.eu/pvg_tools/en/tools.html#PV
P.
Ge, M. P., & Friedrich, J. (2020). Greenhouse Gas
Emissions by Countries and Sectors. World Resources
Institute, 2–11.
Greening, B., & Azapagic, A. (2012). Domestic Heat
Pumps: Life Cycle Environmental Impacts and
Potential Implications for the UK. Energy, 39(1), 205–
17.
Huang, B. J., & Mauerhofer, V. (2016). Life Cycle
Sustainability Assessment of Ground Source Heat
Pump in Shanghai, China. Journal of Cleaner
Production, 119, 207–14.
Johnson, E. P. (2011). Air-Source Heat Pump Carbon
Footprints: HFC Impacts and Comparison to Other
Heat Sources. Energy Policy, 39(3), 1369–81.
Kiss, B., Kácsor, E., & Szalay, Z. (2020). Environmental
Assessment of Future Electricity Mix – Linking an
Hourly Economic Model with LCA. Journal of Cleaner
Production, 264, 121536.
Marinelli, S., Lolli, F., Gamberini, R., & Rimin, B. (2019).
Life Cycle Thinking (LCT) Applied to Residential Heat
Pump Systems: A Critical Review. Energy and
Buildings, 185, 210–23.
Mayer, M. J., Szilágyi, A., & Gróf, G. (2020).
Environmental and Economic Multi-Objective
Optimization of a Household Level Hybrid Renewable
Energy System by Genetic Algorithm. Applied Energy,
269(May), 115058.
Ministry Without Portfolio of Hungary. (2020). Regulation
7/2006 Determining the Energy Performance of
Buildings.
Mota-Babiloni, A., Barbosa, J. R., Makhnatch, P., &
Lozano, J. A., (2020). Assessment of the Utilization of
Equivalent Warming Impact Metrics in Refrigeration,
Air Conditioning and Heat Pump Systems. Renewable
and Sustainable Energy Review, 129, 109929.
Poggi, F., Macchi-Tejeda, H. Leducq, D., & Bontemps. A.
(2008). Refrigerant Charge in Refrigerating Systems
and Strategies of Charge Reduction. International
Journal of Refrigeration, 31(3), 353–70.
Tamas, C. (2013). Building Typology for Energy Modelling
of the Domestic Housing Stock of Hungary.
Parametric Analysis of Greenhouse Gas Emissions of the Technical Building System Alternatives in Detached Houses Retrofitted to nZEB
Level
239