the thermal control strategy to adjust the temperature
set point is easy to implement and saves energy.
Marco Pritoni, 2015, researched other aspects that
also determine comfort and energy savings in air
conditioners other than the use of temperature control
using a thermostat. The result is that temperature
control determines comfort and energy savings.
Besides, comfort is also influenced by; choice of
clothing, use of windows, instructions for children,
and general perception of thermal comfort.
Aldyanto, 2014, researched an adaptive room
temperature regulation system by integrating an
"indoor positioning system" based on Wi-Fi and a
temperature sensor. The results show that by
integrating an indoor positioning system with a
temperature sensor, you can control the room
temperature butter and increase energy savings. The
positioning system can determine the load more
accurately. Thus the indoor temperature setting can
be better adjusted and can improve energy
consumption savings.
Mohamed Elhelw, 2016, has conducted energy
management analysis for heating, ventilation and air
conditioning systems. The energy saved by using the
modified bin method is higher than the
CLTD/CLF/SCL method. Using the modified bin
method will save energy by 45.57% and while the
other methods will save energy by only 33.42%. The
environmental benefits would also be realized with
energy conservation benefits in the long run.
Manjula Siriwardhana, 2017, investigated the
comparison of energy use between standard air
conditioners and inverter type air conditioners
operated in office buildings. The results show that
using inverter technology can save energy up to 35%
compared to use standard air conditioners.
Satish Parman, 2018, conducted an experimental
study of a simple VCRS cycle and a VCRS cycle with
superheating with the help of a liquid line heat
exchanger. If the evaporator temperature increases
before entering the compressor by 6 0C from (-2 0C
to 4 0C i.e. superheating refrigerant) the COP of the
cycle, and the refrigeration effect increases with the
help of superheating. In general, refrigerant R-134A
gives the best results for the same evaporator
temperature, condenser temperature, and cooling rate
compared to refrigerants R-12 and R-717
(Dharmendra, 2014).
This study will investigate the energy profile of
Split air conditioners and system performance. The
energy consumption profile can be used for energy
conservation in increasing the efficiency of energy
use.
2 METODOLOGY
The split type of air conditioning application has a
cooling capacity of 9000 Btu / hr which is made by
Panasonic electric. The sketch of the experimental
equipment design and positioning of the measuring
instrument is shown in Figure-1. Tests are carried out
using refrigerant R32. The observed data include;
refrigeration system pressure, temperature in each
state, current and voltage used, and compressor power
consumption.
A digital AC clamp power analyzer (LT Lutron
DW-6092) use to measure the compressor power
consumption system. Bourdon tube pressure gauge
measures the refrigerant pressure of the out
evaporator which is suitable for the refrigerant system
with the 5. psi accuracy level. In this study, pressure
drops in both condenser and evaporator were ignored
due to the effect on the end of the result was not
significant. The K-type thermocouple records the
temperature in each state of the refrigerant and the air
circulation of the evaporator at predetermined
measurement points.
Based on (Arora, 2011 and Moran, 2004) , the
desired parameter is calculated by using equations (1)
to (4). Equation (1) is used to calculate the
compressor power consumption. Equations (2), (3),
and (4) are used to calculate Mass flow rate, cooling
capacity, and system performance
W
k
= V.I.Cos
ϕ
(1)
m
ref
= Wk/(h
1
-h
2
) (2)
Q
r
= m
ref
.(h
1
-h
4
) (3)
COP = Q
r
/W
k
(4)
In all equations, enthalpy of the out evaporator,
compressor, and expansion are expressed by h
1
, h
2
,
and h
4
consecutively.
Figure 1: Experimental design and instrument tool position.